OT 60/220 240/12 P
Product family benefits
- Versatile scope of application due to output power range of up to 120 W
- Very high efficiency
- IP rating: up to IP67
- High surge protection: up to 3 kV (L-N) / 6 kV (L/N-PE)
Areas of application
- Suitable for indoor and outdoor installations
- Ideal for mounting in very tight spaces
Technical Data
Electrical data
Nominal input voltage
220 240 V
Mains frequency
50 60 Hz
Input voltage AC
198 264 V
Total harmonic distortion
< 20 %
Power factor λ
098/093
Device power loss
9.0 W
Inrush current
35 A
Max. ECG no. on circuit breaker 10 A (B)
11
Max. ECG no. on circuit breaker 16 A (B)
17
Max. ECG no. on circuit breaker 25 A (B)
-
Surge capability (L-N)
3 kV
Nominal output voltage
12.5 V
U-OUT (working voltage)
12.5 V
Nominal output power
60 W
Galvanic isolation
SELV
Galvanic isolation primary/secondary
3.75 kV
Dimensions & weight
Mounting hole spacing, length
171.0 mm
Product weight
70000 g
Cable cross-section, input side
1.0 mm²
Cable cross-section, output side
1.0 mm²
Wire preparation length, input side
10 mm
Wire preparation length, output side
10 mm
Cable/wire length, input side
500 mm
Cable/wire length, output side
500 mm
Width
500 mm
Mounting hole spacing, width
14.0 mm
Length
1800 mm
Height
340 mm
Colors & materials
Casing material
Metal
Temperatures & operating conditions
Ambient temperature range
-25 +55 °C
Maximum temperature at tc test point
80 °C
Max.housing temperature in case of fault
100 °C
Temperature range at storage
-40 +85 °C
Permitted rel. humidity during operation
5 85 %
Lifespan
ECG lifetime
50000 h
Additional product data
Successor EAN
4062172133487
Capabilities
Dimmable
No
Overheating protection
Automatic reversible
Overload protection
Automatic reversible
Short-circuit protection
Automatic reversible
No-load proof
Yes
Suitable for fixtures with prot. class
II
Number of channels
1
Certificates & standards
Approval marks approval
CE / ENEC 18 / CB / CCC / RCM / EAC / BIS
Standards
Acc. to IEC 61347-1/Acc. to IEC 61347-2-13/Acc. to IEC 62384/Acc. to CISPR 15/Acc. to IEC 61000-3-2/Acc. to IEC 61000-3-3/Acc. to IEC 61547
Protection class
II
Type of protection
IP67
Logistical data
Commodity code
850440829000
Environmental information
Information according Art. 33 of EU Regulation (EC) 1907/2006 (REACh)
Date of Declaration
14-04-2022
Primary Article Identifier
4008321790811
Declaration No. in SCIP database
In work
Packaging information
EAN |
Unit |
Piece |
Dimension l x w x h |
Weight |
Volume |
---|---|---|---|---|---|
4008321790811 |
FS
| 1 | |||
4008321790828 |
VS
| 10 | 574mm x 323mm x 137mm | 8650.00g | 25.40dm³ |
Downloads
Information about Family
When it comes to lighting design, you can now set your imagination free, wherever and whatever the space concept you are creating, with a choice of 12 V constant voltage drivers from OSRAM. The compact design of the unit makes these power supplies ideal for mounting in very tight spaces and there are options suitable for use in applications both inside and outside. So, whether you are designing luminaires to create ambience in shops or restaurants, creating LED backlighting or other effects in architainment, or using flexible LED strip lights to integrate paths or handrails, you may find your perfect power supply within this range.
Ecodesign regulation information:
Intended for use with LED modules.
The forward voltage of the LED light source shall be within the defined operating window of the control gear in all operating conditions including dimming if applicable.
Separate control gear and light sources must be disposed of at certified disposal companies in accordance with Directive 2012/19/EU (WEEE) in the EU and with Waste Electrical and Electronic Equipment (WEEE) Regulations 2013 in the UK. For this purpose, collection points for recycling centres and take-back systems (CRSO) are available from retailers or private disposal companies, which accept separate control gear and light sources free of charge. In this way, raw materials are conserved and materials are recycled.
Intended for use with LED modules.
The forward voltage of the LED light source shall be within the defined operating window of the control gear in all operating conditions including dimming if applicable.
Separate control gear and light sources must be disposed of at certified disposal companies in accordance with Directive 2012/19/EU (WEEE) in the EU and with Waste Electrical and Electronic Equipment (WEEE) Regulations 2013 in the UK. For this purpose, collection points for recycling centres and take-back systems (CRSO) are available from retailers or private disposal companies, which accept separate control gear and light sources free of charge. In this way, raw materials are conserved and materials are recycled.
Products
Product |
|
|
|
|
|
Data sheet | ||
---|---|---|---|---|---|---|---|---|
OT 60/220
240/12 P
|
60 W | No | 1800 mm | 500 mm | 340 mm | |||
OT FIT 60/220-240/12 P
|
60 W | No | 1570 mm | 530 mm | 315 mm | |||
OTe 120/110
277/12 E
|
120 W | No | 2580 mm | 512 mm | 445 mm | |||
OT FIT 150/220-240/12 P
|
150 W | No | 2020 mm | 530 mm | 315 mm | |||
OT FIT 300/220-240/12 P
|
300 W | No | 2660 mm | 830 mm | 395 mm |